Tools

Industry-standard calculators.
Real formulas. Real results.

Find the right calculator for the questions our specialists field weekly — pipe sizing, storage capacity, electrical conversions and water-quality checks. Sensible defaults, every field editable, every output in the units you work in.

Cable size calculator

Select the smallest copper cable that meets both ampacity and voltage-drop limits per SANS 10142-1 / IEC 60364, with installation-method and ambient-temperature derating.

Design current
25.5A
= 31.8 A with 25 % margin
Suggested breaker
32A
3-pole MCB / MCCB · 400 V system.
Minimum cable size
6mm² copper
= 2.55 % Vd over 50 m
Driven by ampacity, not voltage drop (voltage drop alone needs only 4 mm²).
Derated ampacity at chosen size
33.8A
After 100 % install × 94 % ambient.

Brief us on your water needs.

For personalised assistance and solutions, contact our specialists.

Contact us