Find the right calculator for the questions our specialists field weekly — pipe sizing, storage capacity, electrical conversions and water-quality checks. Sensible defaults, every field editable, every output in the units you work in.

Plant power & running cost

Add every motor and panel on site, set its kW and daily hours, and the calculator returns the plant's daily / monthly / annual energy, electricity cost and CO₂ footprint.

Equipment nameCategorykWHrs / dayDuty %kWh / day
88
2.88
105
24
57.6
9.6
20.6287
Daily energy
287kWh / day
Monthly energy
8,612kWh / month
Annual energy
104,784kWh / year
= 105 MWh/year
Daily cost
R 718
Monthly cost
R 21,531
Annual cost
R 261,961
Sizing & footprint
Peak connected load
20.6kW
Sum of installed kW — used to size genset, transformer or grid feed.
Average load
12kW
= 14.1 kVA
What the meter actually sees on average across 24 h.
Annual CO₂
99,545kg / year
= 99.5 t / year
At the current grid mix — solar PV displaces this directly.
Electrical sizing — connection, breaker & cable
Recommended phase
Threephase · 400 V
Three phase 400 V required — single-phase mains will not deliver this load.
Design / sizing current
43.7A
= 34.9 A actual (×1.25 margin)
Suggested main breaker
50A
Three-phase 400 V MCB / MCCB.
Minimum cable size
10mm² copper
= 1.24 % Vd over 30 m
Driven by ampacity, not voltage drop (Vd alone needs only 2.5 mm²).
Category breakdown
CategoryItemsInstalled kWkWh / dayShare
High-pressure (RO / UF)17.510536.6 %
Feed / source15.58830.7 %
Booster / distribution1457.620.1 %
Storage / transfer13248.36 %
Auxiliary / panels10.49.63.34 %
Pre-treatment10.182.881 %

Brief us on your water needs.

For personalised assistance and solutions, contact our specialists.